Sungrow Inverter Error Codes

Troubleshooting Sungrow Error Codes

CodeMeaningWhat to do?
0002

The grid voltage exceeds inverter allowable upper limit.

Check the voltage of the grid. If the grid voltage exceeds the permissible range of inverter protection parameters, ask the utility grid company for a solution. If the grid voltage is within the permissible range, contact Sungrow Service Dept.
0003Grid transient voltage exceeds the permissible rangeThis is a short-term fault due to grid conditions. The inverter should fix itself. If the fault still appears, contact Zac Power
0004The grid voltage is below inverter’s allowable lower limit.Check the grid voltage.  If the grid voltage exceeds the permissible range of inverter protection parameters, ask the utility grid company for a solution. If the grid voltage is within the permissible range. If code continues to appear, contact Zac Power
0005The grid voltage is too low.This is a short-term fault due to grid conditions. Inverter should fix itself. If the fault still appears, contact Zac Power
0006The AC output current exceeds inverter allowable upper limit.The inverter will resume if the output current falls below the protection value.  If the fault still appears, contact Zac Power
0007Transient AC overcurrentThe inverter will self-recover after several seconds. If the fault still exists, please contact Sungrow Service Dept.
0008The grid frequency exceeds inverter allowable upper limit.Check the grid frequency. If the grid frequency exceeds the permissible range of inverter protection parameters, ask the utility grid company for a solution. If the grid frequency is within the permissible range, contact Sungrow Service Dept.
0009The grid frequency is below the inverter allowable lower limit.
0010IslandingCheck whether AC circuit breaker is triggered, the cables are firmly connected. Check whether the grid is not in service. If all conditions are OK and this fault still occurs in the LCD screen, contact Zac Power
0011The DC component of AC current exceeds the inverter limit.Inverter should fix itself but if the fault still appears, contact Zac Power
0012A failure current is detected.Check the PV strings for ground fault. If the fault still appears, contact Zac Power
0014The average grid voltage exceeds the permissible range for over 10 minutes.Wait a moment for inverter recovery. Check the voltage of the grid. If the grid voltage exceeds the permissible range of inverter protection parameters, ask the utility grid company for a solution. If the fault still appears, contact Zac Power
0015The grid voltage exceeds the permissible rangeCheck the model of the AC cables. The inverter should fix itself. Wait a moment for inverter recovery. If the grid voltage exceeds the permissible range of inverter protection parameters, contact Zac Power
0016The bus voltage or power is high.Inverter should fix itself. If the fault still appears, contact Zac Power
0019The transient bus voltage is high.
0020The bus voltage is high.
0021PV1 input overcurrent is detectedCheck the layout and the wiring of PV1 input.
0022PV2 input overcurrent is detectedCheck the layout and the wiring of PV2 input.
0036The temperature of radiator is too high.Check whether the placement of the inverter is correct. Check whether the inverter operating ambient temperature is more than the range. Check whether the AC output power exceeds the nominal power. If the fault still appears, contact Zac Power
0037The internal temperature of inverter is too high
0038Relay fault is detectedInverter should fix itself. If the fault still appears, Zac Power
039The insulation resistance is low. (ISO-flt)Check whether the positive and negative of PV panels is short-circuited with ground lead.

Inverter should fix itself. If the fault still appears, contact Zac Power

041Leakage current self-test abnormalityInverter should fix itself. If the fault still appears, Zac Power
047The PV configuration mode set in the phone application interface is not in accordance with the configuration in the connection cabinet.Disconnect the inverter. Re-select PV configuration mode and re-connect PV strings.
048Sampling channel failureInverter should fix itself. If the fault still appears, contact Zac Power
053Auxiliary DSP detects grid voltage exceeds set protection valueCheck the grid voltage. If the grid voltage exceeds the permissible range of inverter protection parameters, ask the utility grid company for a solution. If the fault still appears, contact Zac Power
054Auxiliary DSP detects grid frequency exceeds set protection value
056Auxiliary DSP detects grid leakage current exceeds set protection rangeCheck whether there is a grounded fault of the PV string. If the fault still appears, contact Zac Power
057Auxiliary DSP AC current sampling channel anomalyInverter should fix itself. If the fault still appears, contact Zac Power
058Auxiliary DSP detects AC current DC injection exceeds inverter set protection range
059Main and auxiliary DSP communication anomaly
060Main and auxiliary DSP sampling difference
070Fans are defectiveStop the inverter and disconnect the AC and DC cables. Check whether the fan duct has been blocked. If not, replace fans.
087Arc self-detection anomaly warnWait a while. Contact Zac Power
088Arc anomaly faultStop the inverter and disconnect the AC and DC cables. Check cable connection for aging and looseness. Re-power on and remove the arc warn manually. Contact Sungrow if this fault still occurs.
089Arc detection OFF warnRemove the warning by enabling arc detection function or keep the warn by closing arc detection function.
100The AC output current exceeds inverter protection limit.The inverter will resume if the output current falls below the protection value. If the fault still appears, contact Zac Power
101The grid frequency exceeds inverter allowable upper limit.Check the grid frequency. If the grid frequency exceeds the permissible range of inverter protection parameters, ask the utility grid company for a solution. If the grid frequency is within the permissible range, contact Zac Power
102The grid frequency is below the inverter allowable lower limit.
106The inverter is not groundedCheck whether there is a reliable inverter grounding line, if there is access to the ground, and the fault still exists, please contact Sungrow Service Dept.
200The bus voltage is high.Wait for inverter recovery after bus voltage lower.  If the fault still appears, contact Zac Power
201The bus voltage is too low.
202PV current overcurrentWait for inverter recovery after DC current is reduced. If the fault still appears, contact Zac Power
205AC output replay abnormalInverter should fix itself. If the fault still appears, contact Zac Power
307DC power is too highCheck whether the configuration of PV is in the range indicated in the specification. If the fault occurs repeatedly, contact Sungrow Service Dept.

Zac Power Services

Zac Power offers comprehensive electrical services in Cowra and surrounding areas, boasting over 8 years of experience, licensed electricians, and a commitment to top-notch workmanship and professionalism.

Solar Services
Solar installations, maintenance, panels, inverters, battery & off-grid.
Electrical Services
Zac Power provide top-quality electrical services in Cowra NSW.
Air Conditioning
Expert installation for split systems and ducted air conditioning units.
We focus on delivering a personalised service throughout Cowra and surrounds. Providing a trusted local service to the community and exceed customer satisfaction on every job.